Full overview about TRANSFORMERS
AC power transformers
AC power transformers are one of the keys to allowing widespread distribution of electric power as we see it today. Transformers efficiently convert electricity to higher voltage for long distance transmission and back down to low voltages suitable for customer usage.
The distribution transformer normally serves as the final transition to the customer and often provides a local grounding reference. Most distribution circuits have hundreds of distribution transformers.
Distribution feeders may also have other transformers: voltage regulators, feeder step banks to interface circuits of different voltages, and grounding banks.
What does an AC transformer actually do?
Transformers efficiently converts electric power from one voltage level to another. A transformer is two sets of coils coupled together through a magnetic field. The magnetic field transfers all of the energy (except in an autotransformer). In an ideal transformer (Figure 1), the voltages on the input and the output are related by the turns ratio of the transformer:
V1 = V2 × N1 / N2
where:N1 and N2 are the number of turns andV1 and V2 are the voltage on windings 1 and 2
In a real transformer, not all of the flux couples between windings.
This leakage flux creates a voltage drop between windings, so the voltage is more accurately described by:
V1 = N1 / N2 × V2 – XL × I1
where:XL is the leakage reactance in ohms as seen from winding 1, andI1 is the current out of winding 1.
The current also transforms by the turns ratio, opposite of the voltage as:I1 = I2 × N2 / N1
The ampere-turns stay constant at N1 × I1 = N2 × I2.
This fundamental relationship holds well for distribution and power transformers. A transformer has a magnetic core that can carry large magnetic fields.
The cold-rolled, grain-oriented steels used in cores have permeabilities of over 1000 times that of air. The steel provides a very low-reluctance path for magnetic fields created by current through the windings.
Consider voltage applied to the primary side (source side, high-voltage side) with no load on the secondary side (load side, low-voltage side).
The winding draws exciting current from the system that sets up a sinusoidal magnetic field in the core. The flux in turn creates aback emf in the coil that limits the current drawn into the transformer.
A transformer with no load on the secondary draws very little current, just the exciting current, which is normally less than 0.5% of the transformer’s full-load current.
On the unloaded secondary, the sinusoidal flux creates an open-circuit voltage equal to the primary-side voltage times the turns ratio.
When we add load to the secondary of the transformer,the load pulls current through the secondary winding.
The magnetic coupling of the secondary current pulls current through the primary winding, keeping constant ampere-turns.
Normally in an inductive circuit, higher current creates more flux, but not in a transformer (except for the leakage flux).
The increasing force from current in one winding is countered by the decreasing force from current through the other winding (see Figure 2).
The flux in the core on a loaded transformer is the same as that on an unloaded transformer,even though the current is much higher.
The voltage on the primary winding determines the flux in the transformer (the flux is proportional to the time integral of voltage).
The flux in the core determines the voltage on the output-side of the transformer (the voltage is proportional to the time derivative of the flux).
Figure 3 shows models with the significant impedances in a transformer.
The detailed model shows the series impedances, the resistances and the reactances.
The series resistance is mainly the resistance of the wires in each winding. The series reactance is the leakage impedance.
The shunt branch is the magnetizing branch, current that flows to magnetize the core.Most of the magnetizing current is reactive power, but it includes a real power component.
Power Losses
Generally speaking, power in transformer is lost in the core through the hysteresis and eddy currents. Keep in mind that hysteresis and eddy currents always occur together.
Hysteresis
As the magnetic dipoles change direction, the core heats up from the friction of the molecules. More about hysteresis and how to reduce these losses read in this technical article.
Eddy currents
Eddy currents in the core material causeresistive losses. The core flux induces the eddy currents tending to oppose the change in flux density.
The magnetizing branch impedance is normally above 5,000% on a transformer’s base, so we can neglect it in many cases.
The core losses are often referred to as iron losses or no-load losses. The load losses are frequently called the wire losses or copper losses.
The simplified transformer model in Figure 3 with series resistance and reactance is sufficient for most calculations including load flows, short circuit calculations, motor starting, or unbalance.
Small distribution transformers have low leakage reactances, some less than 1%on the transformer rating, and X/R ratios of 0.5 to 5.
Larger power transformers used in distribution substations have higher impedances, usually on the order of 7 to 10% with X/R ratios between 10 and 40.
The leakage reactance causes voltage drop on a loaded transformer.
The voltage is from flux that doesn’t couple from the primary to the secondary winding.
Blume et al. (1951) describes leakage reactance well. In a real transformer, the windings are wound around a core. The high and low voltage windings are adjacent to each other.
In general, leakage impedance increases with:Higher primary voltage (thicker insulation between windings)kVA ratingLarger core (larger diameter leads to more area enclosed)Leakage impedances are under control of the designer, and companies will make power transformers for utilities with customized impedances.
Large distribution substation transformers often need high leakage impedance to control fault currents, some as high as 30% on the base rating.
Thanks for sharing information about AC power transformers.Visit Servo Automatic Voltage Stabilizer Suppliers in bangalore.
ReplyDelete